For types 48 (door contact), 50 (light), 54 ( surge protection) and 55 (vandalism) the
value (after value mapping if appropriate) can be inverted (see uplink configuration
above). For Types 48, 54 and 55, the default is to invert the value, e.g. a value of “0”
is reported as “door open”, “surge protection defect” or “vandalism alarm”
respectively, and a value “not 0” is reported as “door closed”, “surge protection ok” or
“no vandalism alarm”.
For types 51, 52 and 53, an appropriate value mapping must be configured and
assigned to the sensor channel.
For type 51, a pre-
defined “default” value mapping is applied if there is no value
mapping assigned to the sensor channel
6.1.3.2 Manufacturer defined data types FG6
6.1.3.2.1 Type 151
– status power supply
Position
Description
Value
Byte 1
Length
Length of the de block
Byte 2
Channel
[1..254 ]
Byte 3
DE-Type
[ 151 ]
Byte 4
Supplier-code
47 (Lufft)
Byte 5
See table
BIT
STATUS 0
STATUS 1
0
Power ok (BM=open)
Power failure (BM=closed)
1
UPS ok (BA=open)
UPS defect (BA=closed)
2
n/a
n/a
3
n/a
n/a
4
GFCI (FI) ok
GFCI (FI) fired
5
Circuit breaker (SI) ok
Circuit breaker (SI) off
Содержание 8511.EAK
Страница 1: ...Operating Manual LCom Lufft Communicator Order No 8511 EAK Version V2 18 1 11 2019 www lufft com ...
Страница 41: ...5 8 2 8 essSubSurfaceSensorTable The parameters for the subsurface temperature sensors are configured here ...
Страница 42: ...5 8 2 9 essSnapShotCameraTable The camera s is are configured here See Camera Support below ...
Страница 124: ...Manual LCom Page 124 of 158 The button show events opens a dialog showing the events stored on the device ...
Страница 133: ...Manual LCom Page 133 of 158 reactivated by disconnecting and reconnecting the USB stick wait time 3 seconds ...
Страница 153: ...Manual LCom Page 153 of 158 6 2 Connection Example ...