For each alarm channel following settings are available:
•
DigitalIO Host:
the IP Address or DNS Host name for the digital I/O board
•
IP Port:
the IP Port for Modbus/IP communication (usually 502)
•
I/O Port:
the digital output port number on the digital I/O board. Usually the
numbering starts with 0, i.e. the first output port is number 0 not number 1
•
Invert Output:
if this option is selected, the status of the output port is inverted
to the alarm status, i.e. if the status is
“no alarm” the output is “on”, if the status
is an alarm status the output is “off”.
•
Alarm Mode:
following calculation modes are available:
o
min (underrun):
alarm condition is true if the measure value is below
the configured “Alarm Min” value
o
max (overrun):
alarm condition is true if the measure value is above
the configured “Alarm Max” value
o
value mapping:
alarm condition is calculated using the result of a
value mapping. If the result is 0, no alarm condition is assumed. Any
value other than 0 is treated as an alarm condition.
•
Alarm Min:
in m
ode “min” this value determines the threshold from where on
the alarm condition is set to “true”. In mode “max” this value determines the
Содержание 8511.EAK
Страница 1: ...Operating Manual LCom Lufft Communicator Order No 8511 EAK Version V2 18 1 11 2019 www lufft com ...
Страница 41: ...5 8 2 8 essSubSurfaceSensorTable The parameters for the subsurface temperature sensors are configured here ...
Страница 42: ...5 8 2 9 essSnapShotCameraTable The camera s is are configured here See Camera Support below ...
Страница 124: ...Manual LCom Page 124 of 158 The button show events opens a dialog showing the events stored on the device ...
Страница 133: ...Manual LCom Page 133 of 158 reactivated by disconnecting and reconnecting the USB stick wait time 3 seconds ...
Страница 153: ...Manual LCom Page 153 of 158 6 2 Connection Example ...