12
6.2018
NOTE
Depending on the type of device the delay lasts from 30 to 300 seconds.
3.6 Standby
The device enters standby state when the values of the selected parameters
Heating, Cooling,
DHW
, device protection ... are reached. The display of the interface displays the status:
NOTE
The device enters the standby mode also when any operation protection is active
(compressor start-up delay, insufficient water flow); see chapter 9.
3.7 Operation HP STOP
In case you want to shut down the device, press the
(ENTER) key and hold it for 3 seconds.
The operation of the device is interrupted but the device is still live.
The device can be turned on again by pressing the
(ENTER) key and holding it for 3 seconds.
3.8 Device HP STOP
The device can be disconnected from the power supply by switching the main switch to position “
0
”
or disconnecting the circuit breaker (the electrical power supply fuses).
NOTE
WPL devices must not be disconnected from the power supply for a longer time (via the
main switch or circuit breakers) because by doing so you disable the devices protection
against water freezing in the system which leads to complete device malfunction. Here
the requirements from the installation manual have to be considered.
3.9 Power outage
In case of a power outage the device ceases to operate. After power is restored the device
undergoes 300 seconds of protection mode and then automatically returns to the mode before the
power outage. In the case of a power outage the controller
retains all settings
set before the
outage.
NOTE
In case of a power outage longer than 2 hours air-water models with a water connection,
water has to be drained from the connecting pipes between the external and internal
device. Operate in accordance with the requirements in the installation manual.
Standby…………………………….
Heating
35.5°C
Return
35.3°C
DHW
49.0°C
HP STOP…………………………….
Heating
35.5°C
Return
32.3°C
DHW
49.0°C