The alternative source function is used for using the heat from the solar collectors (SSE) or for using
heat from the biomass DHW s. All settings for the alternative source can be found in the menu
Alternative source
. Heating the storage buffer tank or DHW begins when the temperature of the
alternative source reaches the set temperature difference (parameter
Dif.Min.
) between the
alternative source and the buffer tank or DHW. Heating the buffer tank is performed until the set
temperature in the menu
Alternative source
.
The DHW has heating priority (parameter
Prior. DHW.
). When the temperature in the DHW is
reached (parameter
Set.Temp.
) it is followed by the heating of the buffer tank. After the temperature
of the buffer tank is reached the heating of the DHW is turned on again until the temperature set in
the parameter
Max.Temp
in the menu
Alternative source
is reached. If the temperature of the
alternative source is still higher than the temperature in the buffer tank, heating of the buffer tank
continues until the parameter
Max. Temp.
(The maximum temperature of the buffer tank), set in
the menu
Alternative source
.
When the buffer tank and DHW reach the maximum temperature, heating with the alternative
source stops.
In case the temperature of the alternative source reaches the temperature of protection (parameter
protection
), a signal turns on which can control the users to lower the temperature of the alternative
source.
NOTE
We recommend keeping the settings set by the authorised contractor for commissions.
1.
Press key
(MENU) in the basic menu.
In the user menu choose the menu
Alternative source
with the key
and
press the key
(ENTER).
>
Alternative source <
Backup source
Mode
Temperatures