48
6.2018
Screed drying
NO
Turning on the programme for Screed drying
[YES,
NO
].
Initial
20.0
10.0…50.0
Changing the initial temperature.
Maximum
30.0
10.0…50.0
Setting the highest temperature up to which
the screeds can be heated.
Step
24
10.0… 100.0
Setting the operating hours for the step
[10…
24
] h
Duration
264
10.0… 10000
Maintaining the maximum temperature
reached [100…
264
..1000h].
Final
20.0
10.0…50.0
End temperature.
1. Circ.
Thermostat
Choosing the regulation for 1. Circuit, turned
on via the set value of the thermostat
[
Thermostat
], the spatial corrector [
KT-1/KT-
2
] or constantly on [
ON
] or off [
OFF
].
2. Circ.
Thermostat
Choosing the regulation for 2. Circuit, turned
on via the set value of the thermostat
[
Thermostat
], the spatial corrector [
KT-1/KT-
2
] or constantly on [
ON
] or off [
OFF
].
3. Circ.
Thermostat
Choosing the regulation for 3. Circuit, turned
on via the set value of the thermostat
[
Thermostat
], the spatial corrector [
KT-1/KT-
2
] or constantly on [
ON
] or off [
OFF
].
4. Circ.
Thermostat
Choosing the regulation for 4. Circuit, turned
on via the set value of the thermostat
[
Thermostat
], the spatial corrector [
KT-1/KT-
2
] or constantly on [
ON
] or off [
OFF
].
Reduced
NO
I case the change of the parameter to
YES
the device will operate in a lowered ECO
mode during heating/cooling.
Operation
AUTO
The change of the mode for the whole system
[
AUTO, ECO, COMFORT
].
Mode HP
ON
Turn on [
ON
], off [
OFF
] and [
AUTO
] modes
of setting the parameters. Only when
choosing AUTO operation mode you can set
the schedule for individual parameters. In
case the parameters are set to
ON
the
parameter will be turned on but you will be
unable to change the schedule.
Mode DHW
AUTO
Mode 1. Circ.
AUTO
Mode 2. Circ.
AUTO
Mode 3. Circ.
AUTO
Mode 4. Circ.
AUTO
Mode Temp.
12
0.0… 30.0
The temperature at which the mode changes
3x in a row in case of the
AUTO mode
at
21:00
C/W ALL
I
The correction of the current desired
temperature of the device and all circuits in
the step towards
+ or -.
D8-PV
Rise 1
The buffer tank will switch to the
Comfort
mode upon the signal from outside. You can
find the descriptions of the set value in
chapter 5.11.
Silent mode
Applies only for type of WPLV device. For
settings, see chapter 5.4..
Language
EN
This parameter sets the desired controller
language.
Model:
It affects the correct display on the web
interface Home Cloud.
In case of installing the external unit WPLV
09, set the parameter
Model
to
124.
In case of installing the external unit WPLV
14, set the parameter
Model
to
125.
In other devices, the model does not have to
be changed.
Temperatures
Parameter name
Adjustable
value
Scope
Parameter description
Return
28.0°C
The current temperatures of individual
sensors are shown. The number of sensors
depends on your heating system.
Flow
36.1°C
DHW
48.0°C