6.2018
45
Normal
19.9
19.9…max.
By setting this parameter we change the
desired temperature in the
Normal
operating
mode of the HP.
Eco
–
2.0
–10.0… 0.0
By setting this parameter we change the
desired temperature in the
ECO
operating
mode of the HP.
Comfort
2.0
0.0…10.0
By setting this parameter we change the
desired
temperature
in
the
Comfort
operating mode of the HP.
Hysteresis
2.0
1.0… 10.0
By setting this parameter we change the
Hysteresis
parameter of the mixing valve
from 1,0 °C to 10,0 °C.
Example:
The parameter
HNormal
is 30,0 °C. The
mixing valve will be in standby from 18,0 °C
to 22,0 °C.
In space
22.0
17.0… 27.0
Desired room temperature which can
be set from 17 to 27 °C.
Stan.space
0.5
0.0…2.0
Standby with regulation of the room
temperature.
DHW
Parameter name
Adjustable
value
Scope [°C]
Parameter description
DHW
OFF
25.0…55.0
By changing the parameter
OFF
to the
selected temperature i.e. of 40,0 °C you turn
on the DHW.
Hysteresis
7.0
3.0…10.0
By setting this parameter we change the
desired temperature
Hysteresis
of the
device which means again turning on the
heating of DHW in the
DHW
.
Example:
The parameter
Hysteresis
is 7,0 °C. The
water temperature in the DHW falls from 40,0
°C to 33,0 °C and heating of the DHW turns
on again.
Schedule
For settings see chapter 5.4.
Circulation Sched.
By setting this parameter we enable the
circulation of the water. See chapter 5.4 for
settings, the settings are similar to the ones
for the schedule.
TD
60
The heating temperature for preventing the
development of legionella.
TD every
OFF
By changing the parameter
OFF
to 1...99
days we turn on the thermal disinfection of
water performed every 1...99 days.
Start at
0:00
Setting the start of thermal disinfection (from
00:00 to 21:59).
If the electrical heater is integrated we
recommend the use of this function during the
night so as not to interfere with the heating.
Maximum
2
Maximal allowed time of DHW heating [1…4
hours]. In case of an internal flow electric
heater the max. time is 12 h, in case of a
heater installed in the DHW, the heating can
continue simultaneously.
Eco
-2.0
-10.0…0.0
By setting this parameter we change the
desired temperature in the
ECO
operating
mode of the HP.
Comfort
2.0
0.0…10.0
By setting this parameter we change the
desired
temperature
in
the
Comfort
operating mode of the HP.
Alarm under
30,0
25,0… 50,0
Set an alarm for minimum temperature of
water in DHW. The controller reports failure if
the temperature od DHW does not reach the
Содержание WPG 30