44
6.2018
The parameters are adjusted only in case of active cooling.
T.out. min
30
0.0…55.0
Setting the external temperature above which
the cooling will activate.
max
35
0.0…55.0
Setting the external temperature at which the
cooling will deactivate.
The parameters are adjusted only in case of passive cooling.
Min.Diff.
2
0.0…10.0
The minimal difference between passive
temperature and output temp. of source. The
additional temperature sensor is installed on
the primary side of the passive on the exit.
Checking TP
2400
With this parameter you optimise the
operation of the submersible pump because
if the temperature difference of the input and
output temp. of the groundwater are lower
than Min.Dif, the submersible pump does not
operate. The electronics will turn off the
submersible pump for the time of Checking
TP (10...3600 s) turn it on and check if there
is a need for cooling.
for
300
T.out.min.
20
0.0…55.0
Setting the external temperature above which
the passive cooling will activate.
max
30
0.0…55.0
Setting the external temperature at which the
passive cooling will deactivate.
1. CIRCUIT/
2. CIRCUIT/
3. CIRCUIT/
4. CIRCUIT
Parameter name
Adjustable
value
Scope [°C]
Parameter description
Displayed menus in the heating mode
C/W
I
By setting this parameter we lower the
temperature for up to 4 °C or raise it for up to
4 °C.
Example: I>> means that the currently set
temperature of the circuit (the setting in the
parameter
Normal
) is raised for 2 °C.
Schedule
For settings see chapter 5.4.
Normal
19.9
19.9…max.
By setting this parameter we change the
desired temperature in the
Normal
operating
mode of the HP.
Eco
–
2.0
–10.0… 0.0
By setting this parameter we change the
desired temperature in the
ECO
operating
mode of the HP.
Comfort
2.0
0.0…10.0
By setting this parameter we change the
desired
temperature
in
the
Comfort
operating mode of the HP.
Hysteresis
2.0
1.0… 10.0
By setting this parameter we change the
Hysteresis
parameter of the mixing valve
from 1,0 °C to 10,0 °C.
Example:
The parameter
Hysteresis
is 30,0 °C. The
mixing valve will be in standby from 28,0 °C
to 32,0 °C.
Const.
temperature
Heating with constant temperature
Const.
Temperature
or optimised heating according
to external temperature
Heating Curve
.
Correction
5.0
0.0…15.0
The correction of the breaking point of the
weather curve at outdoor tempe15,0
°C.
In space
22.0
17.0… 27.0
Desired room temperature which can be set
from 17,0 to 27,0 °C.
Stan.space
0.5
0.0…2.0
Standby with regulation of the room
temperature.
Displayed menus in the cooling mode
Schedule
For settings see chapter 5.4.