34
6.2018
5.4 Schedules
5.4.1 Operating mode
Every function (heating, cooling, 1. Circuit, 2. Circuit, 3. Circuit, 4. Circuit, DHW, pool, silent
operation and circulation) can operate in several ways. Setting the operation mode for individual
functions are performed in the schedule for this function.
In heating, cooling, mixing circuits, heating of DHW and swimming pool heating there can be 4
different types of operation:
►
OFF
: Heating/cooling is disabled.
►
HEA
of
COL
: Operation in the heating or cooling mode (parameter
Normal
).
►
ECO
: In this mode the controller maintains the temperature which is lower by the value of
the
ECO
parameter than the set temperature in the parameter
Normal
. In case of cooling
the temperature set in this mode is higher by the value of the
ECO
parameter than the set
temperature in the parameter
Normal
. In this mode operation is more economical.
►
COM:
In this mode the controller maintains the temperature which is higher by the value of
the
COM
parameter than the set temperature in the parameter
Normal
. In case of cooling
the temperature set in this mode is lower by the value of the COM parameter than the set
temperature in the parameter
Normal
. In this mode operation is less economical,
depending on the setting it can also be more comfortable.
In circulation of DHW two operation settings are possible:
►
OFF
: Circulation pump is disabled.
►
CIR
: Circulation pump is truned on.
Devices of the WPLV type enable two additional operation modes set in the menu
Mode
with the
parameter
Silent mode
:
►
NRM:
Normal operation in the heating or cooling mode.
►
LOW
: Lowered operation mode in the heating or cooling mode. Lower noise level but also
lower heating or cooling capacity.
5.4.2 Setting operation schedules
NOTE
The easiest way to set the timetable is via the web application for remote control Cloud
(cloud.KRONOTERM.com). For the use of the web interface see Instructions for use
Web interface.
The schedule enables daily settings of 6 operation mode switches. Below is a description of heating
with an example of a daily schedule.
Heating is turned off (OFF) from 00:00 to 02:00.
0
2
4
6
8
10
12
14
16
18
20
22
24
Time of day [h]
COMFORT
Normal
OFF
ECO
Содержание WPG 30
Страница 62: ...62 6 2018 ...
Страница 63: ...6 2018 63 ...