46
6.2018
set temperature under
Alarm under
three
times in a row.
Max ope.
600
0… 999
The maximum heating time of DHW
Time sta.
30
0… 999
The standby of DHW heating
POOL
Setting the parameters of swimming pool heating. Display and configuration options if swimming pool
heating is active (an expansion module is necessary).
Parameter name
Adjustable
value
Scope [°C]
Parameter description
Schedule
For settings see chapter 5.4.
Normal
OFF
19.9…max.
By setting this parameter we change the
desired temperature in the
Normal
operating
mode of the HP.
Eco
–
2.0
–10.0… 0.0
By setting this parameter we change the
desired temperature in the
ECO
operating
mode of the HP.
Comfort
2.0
0.0…10.0
By setting this parameter we change the
desired
temperature
in
the
Comfort
operating mode of the HP.
Hysteresis
3.0
0.1… 1000
By setting this parameter you change the
desired temperature
Hysteresis of the
device.
Example:
The parameter
Normal
is 50,0 °C. The
device will be in standby from 47,0 °C to 50,0
°C.
Minimum
30
30… 1999
In case a need arises for heating the DHW
which has always priority to
Pool Heating
,it
will begin after the elapsed time of the delay
set in the parameter
Minim
um In our case
this is after 30 minutes.
HP SET
45.0
20.0…60.0
Setting the maximum temperature of the
return by heating with device.
Hysteresis
4.0
1.0… -10.0
Temperature difference of standby.
ALTERNATIVE
SOURCE
Setting heating and DHW support with the alternative source (solar collectors, solid fuel DHW ...).
Display and configuration options if the alternative source is active (an expansion module is
necessary).
Parameter name
Adjustable
value
Scope [°C]
Parameter description
---Heating---
Setting heating support. Additional sensor in
the buffer tank.
Set. Temp.
60.0
20.0…80.0
Setting the desired temperature in the buffer
tank.
Dif. Temp.
15.0
7.0…20.0
Min. difference between the temp. of the
buffer tank and temp. of the alternative
source to turn on the HP-AOG of the
alternative source.
Max. Temp.
80.0
60.0…90.0
Max. allowed temperature in the buffer tank
up to which heating will be performed if the
alternative source will have a high enough
temperature.
Min. temp.
40.0
20.0…70.0
The minimal temperature alternative source
up to which the alternative source will heat
the buffer tank.
---Water heater ---
Settings for heating support for DHW. The
DHW sensor is used (basic module).
Set. Temp.
60.0
20.0…80.0
Setting the desired temperature in the DHW.
Dif. Temp.
15.0
7.0…20.0
Min. difference between the temp. of the
DHW and temp. of the alternative source to
turn on the HP-AOG of the alternative source.
Max. Temp.
70.0
60.0…90.0
Max. allowed temperature in the buffer tank
up to which heating will be performed if the
alternative source will have a high enough
temperature.