6.2018
51
DHW-Res.source......
Heating is performed only by selected (internal or external)
additional heat source, compressor is not working. Additional
heat source is switched on manually.
Standby.............
The device is in standby mode because there is no need for
heating/cooling or it is in protection mode.
--REMOTE--SHUT-
OFF--
Remote deactivation (external signal) of the device is active.
Heating - Biv.Alt.
Selected (internal or external) additional heat source is working
in bivalent alternative mode. Additional heat source is active and
compressor is idle because ambient temperature is below
bivalent point. Switching on the additional source is described in
the section 4.6.
DHW - Biv.Alt.
----Overheating-----
The device operates in the thermal disinfection mode.
DEFROST
The device is in the evaporator defrost mode (only WPL/WPLV).
-Comp.temp too high-
Too high compressor temperature.
---? Efficiency ?---
The device does not heat (does not generate enough heat).
Defrost T.Flow ALARM
Alarm; the water temperature of the return during defrost was too low.
------ Max dT ------
The temperature difference between the supply and return is too high.
ERROR
HeatSourceTemp
Source temperature is outside the operating range.
--MODULE 3 - ALARM-
-
Malfunction of one of the modules. The device will restart
automatically after the error is resolved.
--MODULE 4 - ALARM-
-
--MODULE 2 - ALARM-
-
--MODULE 1 - ALARM-
-
-- RESET MODUL 1 ---
One of the modules is in the self-reset process.
-- RESET MODUL 2 ---
-- RESET MODUL 3 ---
-- RESET MODUL 4 ---
Caution flow :
The flow switch is not closed – there is no or not enough water
flow through the device. If there is no or not enough water flow
through device in 120 s, the device goes into compressor
protection mode (Standby). When protection mode elapses, it
tries to start again.
ERROR ..Sensor...... 1
Alarm; one of the sensors is not connected or is damaged.
ERROR ..Sensor...... 2
ERROR ..Sensor...... 3
ERROR ..Sensor...... 4
ERROR ..Sensor...... 5
ERROR ..Sensor...... 6
ERROR ..Sensor...... 7
ERROR ..Sensor...... 8
ERROR ..Sensor...... 9
ERROR ..Sensor...... 10
ERROR ..Sensor...... 11
ERROR ..Sensor...... 12
ERROR ..Sensor...... 13
ERROR ..Sensor...... 15
Содержание WPG 30
Страница 62: ...62 6 2018 ...
Страница 63: ...6 2018 63 ...