6
OPERATION
74
OPTIFLEX 1300 C
www.krohne.com
01/2008 • 4000172301 - HB OPTIFLEX 1300 R02 en
12
output 2: error
handling
5
This sets the behaviour
of current output 2 if an
error occurs. Hold
Hold
Hold
Hold
means that the output
current stays at the
value where the error
occurred. Hold
Hold
Hold
Hold is not
available if 3.8
…
20.5 mA
(NAMUR) is the output
range.
3.6 mA, 22 mA, Hold
22 mA
13
settings summary
read only
save / cancel
save, cancel
3
save
A.1.6
snapshot
Use this to find and filter
out parasite signals in
user-defined areas
along the probe. Empty
the tank before you do
this procedure.
Warning: the level
should be out of
the snapshot area.
1
snapshot start
distance
min-max: detection
delay...sensor length
0.1 m /
0.328 ft
2
snapshot end
distance
Sensor length
Sensor
length
3
snapshot
recording
Is the tank empty? If not,
empty the tank before
taking a snapshot.
yes/no
yes
4
snapshot
recording in
progress
…
5
snapshot
activation
Use this data to filter out
parasite signals.
yes/no
yes
6
settings summary
A.1.7
auto probe length
Use this to correct the
length of the probe if it
was shortened on site.
Warning: this
function should be
used only when the
tank is empty.
1
settings summary
A summary of probe
data (probe type,
counterweight type,
probe end pulse).
2
auto probe length
Do you want to start the
scan?
yes/no
yes
3
auto probe length
in progress
…
4
probe length
Save the new value.
yes/no
yes
Menu No. Step
Function
Function description
Selection list
Default
HB_OPTIFLEX1300_EN_D4_080428.book Page 74 Tuesday, April 29, 2008 2:47 PM