ATEX: SUPPLEMENTARY INSTRUCTIONS
118
OPTIFLEX 1300 C
www.krohne.com
01/2008 • 4000172301 - HB OPTIFLEX 1300 R02 en
7.3.5 EEx d [ia] equipment
General notes
EEx d [ia]-approved equipment have two separate compartments. The electronics block
compartment is Ex ia-approved and the terminals compartment is Ex d-approved.
How to connect the electrical cables
•
Use only flameproof and EEx d-approved cable entries and plugs.
•
If you use only one cable entry, seal the other one with an EEx d-approved plug.
•
All EEx d-approved installations must agree with European standard EN 50018.
Conduit entries
•
Connect the instrument to an EEx d-approved conduit system.
•
Install the applicable EEx d-approved sealing device. For more data, refer to European
Standard EN 50018.
Figure 7-7:
Compartments in EEx d [ia]-approved equipment
1
Ex ia compartment
2
Terminal (Ex d) compartment
1
2
NOTE!
If you must open the Ex ia compartment and remove the electronics blocks for servicing, it is not
necessary to disconnect the wires in the Ex d compartment.
INFORMATION!
Cable entries are supplied on customer demand. If you supply the cable entries, this part must
have a degree of ingress protection IP
≥
6x (EN 60529).