OPERATION
6
69
OPTIFLEX 1300 C
www.krohne.com
01/2008 • 4000172301 - HB OPTIFLEX 1300 R02 en
Menu No. Step
Function
Function description
Selection list
Default
A.1.2
application
Follow this procedure to
describe the tank
contents.
1
information: probe
type
read only
2
product type
The application.
liquid, solid
3
air gap / no air
gap?
This tells the instrument
whether or not there is
air or gas above the
product.
air gap, no air gap
1
air gap
4
number of
products
The number of products
in the tank.
1, 2, >2
1
1
5
top product class
liquid: alcohol, base,
hydrocarbon, liquid
gas, mineral oil,
solvent, aqueous
solution, other
solid: cereals,
minerals, plastic,
other
6
application type
level, interface, level
and interface
2
7
mixed / unmixed?
If there are 2+ liquids in
the tank, is there an
emulsion in the tank.
This tells the instrument
to look for the interface
when the two liquids
have settled.
mixed, unmixed
unmixed
8
settings summary
9
save / cancel
save, cancel
3
HB_OPTIFLEX1300_EN_D4_080428.book Page 69 Tuesday, April 29, 2008 2:47 PM