The message can be classified as either a fault, a warning or an operational message.
If exceeding the switching point is classified as a fault, the controller goes into the fault state
when the signal continues and shuts down the machine.
The following messages can be output:
Message
Explanation
Measured
value
Output
AnMod_p_1
Customised monitoring of the pressure value p1
AnMod_p_2
Customised monitoring of the pressure value p2
AnMod_p_3
Customised monitoring of the pressure value p3
AnMod_p_4
Customised monitoring of the pressure value p4
AnMod_T_1
Customised monitoring of the temperature value T1
AnMod_T_2
Customised monitoring of the temperature value T2
AnMod_T_3
Customised monitoring of the temperature value T3
AnMod_T_4
Customised monitoring of the temperature value T4
AnMod_I_1
Customised monitoring of the current value I1
AnMod_I_2
Customised monitoring of the current value I2
T-Switch inlet
temperature
Customised monitoring of the intake temperature
p-Switch pi
Customised monitoring of internal pressure pi in the oil sep‐
arator tank
T-Switch ADT
Customised monitoring of the airend discharge temperature
ADT
p-Switch pN
Customised monitoring of local network pressure pNloc at
compressor output
T-Switch PDT
Customised monitoring of the compressed air discharge
temperature
Tab. 78 Assigned analogue measured values
Overview
Use the
Analogue values or Switch menus for specifying the settings.
■ Enter the message text
■ Select and activate measured value
■ Set the time delay
■ Setting the logic
■ Selecting the message type
■ Assign and activate the output
Below, the settings are displayed based on an example in the
Analogue values menu. Use the
Switch menu analogously for specifying the settings.
8.12.3.1 Analogue values menu
Precondition The electrical connection has been made.
Access level 2 is activated.
8
Initial Start-up
8.12 Setting input and output signals
160
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
No.: 9_9450 12 E