Display further parameters
1. Use «Up» or «Down» to select the
Cut-in pressure min line.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.2.2 Pressure settings
Menu
System pressure low
☐
↓
<
5.0bar ¦ SD:
0.50bar
ta:
600s
DOR1.03
☐¦Logic:
+
------------------------------
Cut-in pressure min :
5.0bar
Active line
2. Select further parameters with the «Up» and «Down» keys.
8.5.2 Setting pressure parameters
8.5.2.1 Setting the network nominal pressure: pA and pB
The pressure parameters can only be set within certain limits:
Rated machine pressure ≥ SP: pA /pB ≥ Min. cut-in pressure* + switching differential
Tab. 56 Setting limits for the network nominal pressure (* Cut-in pressure min)
The machine switches to LOAD under the following condition:
Network pressure ≤ SP: pA /pB + switching differential
Tab. 57 Pressure condition for LOAD
The machine switches to IDLE under the following conditions
12)
:
Network pressure = Network nominal pressure
2)
Tab. 58 Pressure conditions for IDLE
12)
2)
for machines with frequency converter (SFC): Network pressure = Network nominal pr
ΔpFC
12)
not for SXC
Precondition Access level 2 is activated
1. Open the 5.2.2
<Configuration – Pressure control – Pressure settings> menu.
2. Use «Up» or «Down» to select the
pASP line.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.2.2 Pressure settings
Menu
Setpoint pressure
pA SP:
8.0bar ¦ SD:
−0.5bar
Active line
pB SP:
7.5bar ¦ SD:
−0.4bar
·········
System pressure low
☐
↓
<
5.0bar ¦ SD:
0.50bar
8
Initial Start-up
8.5
Pressure parameters of the machine
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
91