Set the slave number
You must set the slave address for the communication with the SIGMA AIR MANAGER.
When connected to a SIGMA AIR MANAGER, the slave address is determined as follows:
Compressor number used at SIGMA AIR M102.
Precondition Access level 2 is activated.
1. Open the 8.2
<Communication – Com-Module> menu.
The
Com-Module menu is displayed
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
8.2 Com-Module
Menu
Send/receive
Com-Module active
:
☑
Active line
Reset
:
☐
Slave No. :
103
·········
Communication error
:
☑
2. Use «Up» or «Down» to select the
SlaveNo. line.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
8.2 Com-Module
Menu
Send/receive
Com-Module active
:
☑
Reset
:
☐
Slave No. :
103
Active line
·········
Communication error
:
☑
3. Press «Enter».
The display for the slave address flashes.
4. Use «Up» or «Down» to set the slave address 104.
5. Press «Enter».
The setting is applied.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
8.2 Com-Module
Menu
Send/receive
Com-Module active
:
☑
Reset
:
☐
Slave No. :
104
Active line
·········
Communication error
:
☑
Monitoring for communication malfunction is active.
Result Slave address
104 is set.
8
Initial Start-up
8.11 Setting the machine for master control operation
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
131