2. Press «Enter».
The
td delay time flashes.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.7.3.1 External message 1
Menu
External message 1
Message text
DI1.07
ok ☑
Input selected
td:
0s ¦ Logic :
+
set time delay td
DOR1.04
☐
Warning
☑
Example: Warning message type
3. Use «Up» or «Down» to set the time delay in seconds.
4. Press «Enter».
Result The
td delay time has been set.
8.12.2.5 Setting the logic
Possible logic settings
Message at
Sign
24 V
+
0 V
-
Tab. 77 Logic settings
1. Use «Up» or «Down» to select the
td line.
2. Press the «Right» arrow.
3. Press «Enter».
The control field
Logic flashes.
4. Use «UP» or «Down» to set the desired behaviour, see table 77.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.7.3.1 External message 1
Menu
External message 1
Message text
DI1.07
ok ☑
Input selected
td:
0s ¦ Logic :
+
active line, set logic control field
DOR1.04
☐
Warning
☑
Example: Warning message type
5. Press «Enter».
Result For messages at 24 V, the logic is set with the + symbol.
8.12.2.6 Setting the message type
1. Select the message type line with the «Up» and «Down» keys.
8
Initial Start-up
8.12 Setting input and output signals
158
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
No.: 9_9450 12 E