8.11.5.1 Establish the electrical connection for remote LOAD contact (excerpt)
Machine (example)
Fig. 38 LOAD remote contact
1
Electrical connection DI 1.07
2
LOAD remote contact open (IDLE)
3
Electrical connection DI 1.07
4
LOAD remote contact closed (LOAD)
5
SIGMA AIR MANAGER BASIC contacts
➤ Establish the electrical connection for DI 1.07 according to the wiring diagram.
8.11.5.2 Setting the remote LOAD contact operating mode and assigning the input for LOAD remote contact
Precondition Access level 2 is activated.
Set the LOAD remote contact operating mode
1. Open the 5.2.3
<Configuration – Pressure control – Load control> menu.
2. Use «Up» or «Down» to select the
Remote mode line.
3. Press «Enter».
The currently active operating mode
Remote mode flashes.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.2.3 Load control
Menu
Local mode:
pA/pB Cycle
Remote mode:
Load RC
active line
------------------------------
▶1 pA/pB Clock
·········
pA/pB Cycle
4. Use «Up» or «Down» to set the
Load RC input.
5. Press «Enter».
The LOAD remote contact operating mode is set.
8
Initial Start-up
8.11 Setting the machine for master control operation
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
141