8.11.7 Setting the nominal pressure pre-selection via remote contact
The signal to changeover from nominal pressure
pA to nominal pressure pB comes from an input
contact. If a signal is activated at the input, the nominal pressure is regulated to
pB.
Overview
■ Setting up remote contact mode pA/pB
■ Assigning the remote contact input
■ Activating the remote control
➤ Set the nominal pressure pre-selection as described.
8.11.7.1 Setting up remote contact mode pA/pB
Precondition The electrical connection is made.
Access level 2 is activated.
1. Open the 5.2.3
<Configuration – Pressure control – Load control> menu.
2. Use «Up» or «Down» to select the
Remote mode line.
3. Press «Enter».
The currently active operating mode flashes.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.2.3 Load control
Menu
Local mode
:
pB
Remote mode
:
pA/pB RC
Active line
------------------------------
▶1 pA/pB Clock
·········
pA/pB Cycle
4. Use «Up» or «Down» to set the
pA/pB RC input.
5. Press «Enter».
Result The
pA/pB RC operating mode is set.
8.11.7.2 Assigning the remote contact input
A spare input can be found in the machine circuit diagram.
1. Use «Up» or «Down» to select the
pA/pB RC line.
8
Initial Start-up
8.11 Setting the machine for master control operation
146
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
No.: 9_9450 12 E