Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-97-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
terminals
frequency
changing
ratio
P08.46
DOWN
terminals
frequency
changing
ratio
0.01~50.00Hz/s
0.50Hz/s
○
P08.47
Frequency
setting at
power loss
0x000~0x111
LED ones: Action selection when power off.
0: Save when power off
1: Clear when power off
LED tens: Action selection when Modbus set
frequency off
0: Save when power off
1: Clear when power off
LED hundreds: Reserved
0x000
○
P08.48
High bit of
initial power
consumption
This parameter is used to set the original value of the
power consumption.
Original value of power consumption
=P08.48*1000+P08.49
Setting range of P08.48: 0~59999 kWh(k)
Setting range of P08.49: 0.0~999.9 kWh
0°
○
P08.49
Low bit of
initial power
consumption
0.0°
○
P08.50
Magnetic
flux braking
This function code is used to enable magnetic flux.
0: Invalid.
100~150: The bigger the coefficient, the stronger the
braking is.
This inverter is used to increase the magnetic flux to
decelerate the motor. The energy generated by the
motor during braking can be converted into heat
energy by increasing the magnetic flux.
The inverter monitors the state of the motor
0
○
Содержание Goodrive GD300-19-004G-4
Страница 1: ...Series Open Loop Vector Inverter Special for Hoist Goodrive300 19 GD300 19 5R5G 4...
Страница 33: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 32...
Страница 129: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 128...
Страница 135: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 134...
Страница 255: ...201610 V2 0 66001 00230 I I...