Goodrive300-19 series open loop vector inverter special for hosit Communication protocol
-226-
commands, the corresponding function code is P07.27~P07.32 and corresponding parameter
address is 071BH~0720H (there are 6 from 071BH).
The command sent to the inverter:
If the response message is as below:
See from the returned data, all fault types are 0023H (decimal 35) with the meaning of maladjustment
(STo).
10.4.7.2 Example of writing command 06H
Example 1: Make the inverter with the address of 03H to run forward. See table 1, the address of
“communication control command” is 2000H and forward running is 0001. See the table below.
The command sent by the master:
If the operation is success, the response may be as below (the same with the command sent by the
master):
Example 2: Set the Max. output frequency of the inverter with the address of 03H as100Hz.
Содержание Goodrive GD300-19-004G-4
Страница 1: ...Series Open Loop Vector Inverter Special for Hoist Goodrive300 19 GD300 19 5R5G 4...
Страница 33: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 32...
Страница 129: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 128...
Страница 135: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 134...
Страница 255: ...201610 V2 0 66001 00230 I I...