Goodrive300-19 series open loop vector inverter special for hosit Fault tracking
-199-
8.6.5 Abnormal heat of the motor
Check if there is
abnormal heat to the
motor
Set right
motor
parameters
Check if it needs to carry
out parameter autotune
Parameter
autotune
Check if the inverter runs at low
speed all the time
Select right
motor
Low the load
Change the
motor
Set proper
carrier
frequency
Add output
filter
If it is the inverter fault,
please contact with our
company
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Check if the parameter is
right or not
Check if it is variable
frequency motor
Check if the load is too
heavy
Check if the 3-phase
motor is balanced
Check if the carrier
frequency is too low
Check if the motor wire
is too long