Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-69-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
frequency of
motor 2
overcurrent may occur. These phenomena can be
canceled by adjusting this parameter.
The setting range of P04.23: 0~100
The setting range of P04.24: 0~100
The setting range of P04.25: 0.00Hz~P00.03 (the
Max. frequency)
P04.24
Vibration
control factor
at high
frequency of
motor 2
10
○
P04.25
Vibration
control
threshold of
motor 2
30.00Hz
○
P04.26
Energy-
saving
operation
0: No operation
1: Automatic energy-saving operation
Motors will automatically adjust the output voltage to
save energy at light loads.
0
◎
P04.27
Voltage
setting
Select the output setting channel at V/F curve
separation.
0: Keypad: the output voltage is determined by
P04.28.
1: AI1
2: AI2
3: AI3
4: HDI
5: Multi-step speed
6: Reserved
7: Modbus communication
8~10: Reserved
Note: 100% corresponds to the rated voltage of
the motor.
0
○
P04.28
Keypad
setting
voltage
The function code is the voltage displaying when the
voltage is set through keypad.
The setting range: 0.0%~100.0%
100.0%
○
P04.29
Voltage
Voltage increasing time is the time when the inverter
5.0s
○
Содержание Goodrive GD300-19-004G-4
Страница 1: ...Series Open Loop Vector Inverter Special for Hoist Goodrive300 19 GD300 19 5R5G 4...
Страница 33: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 32...
Страница 129: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 128...
Страница 135: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 134...
Страница 255: ...201610 V2 0 66001 00230 I I...