Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-101-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
action
selection
than the ratio of output frequency because of the big
load during ACC running. It is necessary to take
measures to avoid overcurrent fault and the inverter
trips.
0x00~0x11
Ones: current limit
0: Invalid
1: Valid
Tens: overload alarm of hardware current limit
0: Valid
1: Invalid
P11.06
Automatic
current limit
During the running of the inverter, it will detect the
output current and compare it with the limit level
defined in P11.06. If it exceeds the level, the inverter
will run at stable frequency in ACC running, or the
inverter will derate to run during the constant running.
If it exceeds the level continuously, the output
frequency will keep on decreasing to the lower limit. If
the output current is detected to be lower than the
limit level, the inverter will accelerate to run.
Setting range of P11.06: 50.0~200.0%
Setting range of P11.07: 0.00~50.00Hz/s
160.0%
◎
P11.07
Frequency
decreasing
ratio during
current limit
10.00Hz/s
◎
P11.08
Overload
pre-alarm of
motor/inverter
The output current of the inverter or the motor is
above P11.09 and the lasting time is beyond P11.10,
overload pre-alarm will be output.
0x000
○
Содержание Goodrive GD300-19-004G-4
Страница 1: ...Series Open Loop Vector Inverter Special for Hoist Goodrive300 19 GD300 19 5R5G 4...
Страница 33: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 32...
Страница 129: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 128...
Страница 135: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 134...
Страница 255: ...201610 V2 0 66001 00230 I I...