Goodrive300-19 series open loop vector inverter special for hosit Basic operation instruction
-137-
source
2: AI2 (the same as above)
3: AI3 (the same as above)
4: HDI (the same as above)
5: Modbus communication (the same as above)
6~8: Reserved
P03.20
Keypad
setting of
electromotion
torque
0.0~300.0% (motor rated current)
180.0%
P03.21
Keypad
setting of
braking
torque
0.0~300.0% (motor rated current)
180.0%
P17.09
Output torque -250.0~250.0%
0.0%
P17.15
Torque
reference
-300.0%~300.0% (the rated current of the motor)
0.0%
7.6 Parameters of the motor
Physical accident may occur if the motor starts up suddenly during autotune.
Please check the safety of surrounding environment of the motor and the load
before autotune.
The power is still applied even when the motor stops running during static
autotune. Please do not touch the motor until the autotune is completed, otherwise
there would be electric shock.
Do not carry out the rotation autotune if the motor is coupled with the load.
Otherwise, misaction or damage may occur to the inverter or the mechanical
devices. During rotation autotune on the motor which is coupled with load, the
motor parameter may not be counted correctly and misaction may occur. If
necessary, de-couple the motor from the load during autotune.
Goodrive300-19 series inverters can support two sets of motor parameters which can shift between
two motors through multi-function digital input terminal or communication.
Содержание Goodrive GD300-19-004G-4
Страница 1: ...Series Open Loop Vector Inverter Special for Hoist Goodrive300 19 GD300 19 5R5G 4...
Страница 33: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 32...
Страница 129: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 128...
Страница 135: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 134...
Страница 255: ...201610 V2 0 66001 00230 I I...