Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-66-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
When the torque boost is set to 0.0%, the inverter is
automatic torque boost.
Torque boost threshold: under the threshold, the
torque boost is valid, but over the threshold, the
torque boost is invalid.
The setting range of P04.01: 0.0%: (automatic)
0.1%~10.0%
The setting range of P04.02: 0.0%~50.0%
P04.03
V/F
frequency 1
of motor 1
When P04.00=1, the user can set V/F curve through
P04.03~P04.08.
V/F is generally set according to the load of the motor.
Note: V1
<
V2
<
V3, f1
<
f2
<
f3. Too high low
frequency voltage will heat the motor excessively
or cause damage. The inverter may stall when
overcurrent or overcurrent protection.
The setting range of P04.03: 0.00Hz~P04.05
The setting range of P04.04: 0.0%~110.0% (the rated
voltage of motor 1)
The setting range of P04.05: P04.03~P04.07
The setting range of P04.06: 0.0%~110.0% (the rated
0.00Hz
○
P04.04
V/F
voltage 1 of
motor 1
00.0%
○
P04.05
V/F
frequency 2
of motor 1
00.00Hz
○
P04.06
V/F
voltage 2 of
motor 1
00.0%
○
P04.07
V/F
frequency 3
of motor 1
00.00Hz
○
P04.08
V/F
voltage 3 of
motor 1
00.0%
○
Содержание Goodrive GD300-19-004G-4
Страница 1: ...Series Open Loop Vector Inverter Special for Hoist Goodrive300 19 GD300 19 5R5G 4...
Страница 33: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 32...
Страница 129: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 128...
Страница 135: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 134...
Страница 255: ...201610 V2 0 66001 00230 I I...