Goodrive300-19 series open loop vector inverter special for hosit Installation guidelines
-19-
Installation guidelines 4
4.1 What this chapter contains
The chapter describes the mechanical installation and electric installation.
Only qualified electricians are allowed to carry out what described in this chapter.
Please operate as the instructions in
Safety precautions
. Ignoring these may
cause physical injury or death or damage to the devices.
Ensure the power supply of the inverter is disconnected during the operation.
Wait for at least the time designated until the POWER indicator is off after the
disconnection if the power supply is applied. It is recommended to use the
multimeter to monitor that the DC bus voltage of the drive is under 36V.
The installation and design of the inverter should comply with the requirement of
the local laws and regulations in the installation site. If the installation infringes
the requirement, our company will exempt from any responsibility. Additionally, if
users do not comply with the suggestions, some damage beyond the assured
maintenance range may occur.
4.2 Mechanical installation
4.2.1 Installation environment
The installation environment is the safeguard for a full performance and long-term stable functions of
the inverter. Check the installation environment as followings:
Environment
Conditions
Installation site
Indoor
Environment
temperature
-10~+50°C
If the ambient temperature of the inverter is above 40°C, derate 1% for
every additional 1°C.
It is not recommended to use the inverter if the ambient temperature is
above 50°C.
In order to improve the reliability of the device, do not use the inverter
if the ambient temperature changes frequently.
Please provide cooling fan or air conditioner to control the internal
ambient temperature below the required one if the inverter is used in a
close space such as in the control cabinet.
When the temperature is too low, if the inverter needs to restart to run
after a long stop, it is necessary to provide an external heating device
Содержание Goodrive GD300-19-004G-4
Страница 1: ...Series Open Loop Vector Inverter Special for Hoist Goodrive300 19 GD300 19 5R5G 4...
Страница 33: ...Goodrive300 19 series open loop vector inverter special for hosit Installation guidelines 32...
Страница 129: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 128...
Страница 135: ...Goodrive300 19 series open loop vector inverter special for hosit Basic operation instruction 134...
Страница 255: ...201610 V2 0 66001 00230 I I...