Appendix A Parameter Table
- 98 -
Para.
No.
Para. Name
Setting Range
Default
Property
F1-37
Auto-tuning selection
0: No operation
1: Asynchronous motor static auto-
tuning
2: Asynchronous motor no-load
complete auto-tuning
3: Asynchronous motor static
complete auto-tuning
4: Asynchronous motor inertia auto-
tuning (only FVC)
11: Synchronous motor no-load
partial auto-tuning (back EMF
exclusive)
12: Synchronous motor dynamic no-
load auto-tuning
13: Synchronous motor static
complete auto-tuning
14: Synchronous motor inertia auto-
tuning (only FVC)
0
★
Group F2: 1st Motor Vector Control Parameters
F2-00
Speed loop
proportional gain Kp at
low speed
1 to 200
Asynchronous
motor: 30
Synchronous
motor: 20
☆
F2-01 Speed loop integral
time Ti at low speed
0.001s to 10.000s
0.500s
☆
F2-02 Switchover frequency 1 0.00 to switchover frequency 2 (F2-
05)
5.00 Hz
☆
F2-03
Speed loop
proportional gain Kp at
high speed
1 to 200
20
☆
F2-04 Speed loop integral
time Ti at high speed
0.001s to 10.000s
1.000s
☆
F2-05 Switchover frequency 2 F2-02 (Switchover frequency 1) to
maximum frequency (F0-10)
10.00 Hz
☆
F2-06 SVC/FVC slip
compensation gain
50% to 200%
100%
☆
F2-07 Speed feedback filter
time
0.000s to 0.100s
0.004s
☆
F2-08 SVC/FVC deceleration
over-excitation gain
0 to 200
64
☆