Appendix A Parameter Table
- 109 -
Para.
No.
Para. Name
Setting Range
Default
Property
F5-04
DIO1 function selection
37: Frequency lower limit reached
(having output at stop)
38: Abnormality output (direct
output at fault or warning)
39: Motor overheat pre-warning
40: Current running time reached
41: Fault output 2 (output at coast to
stop/decelerate to stop, no output at
undervoltage)
43: Position lock enabled (deviation
pulses < F6-25)
(End)
0
☆
F5-06 FMP output function
selection
0: Running frequency
1: Set frequency
2: Output current
3: Output torque (100.0%
corresponds to 2 times of rated
motor torque)
4: Output power
5: Output voltage (100.0%
corresponds to 1.2 times of rated
drive voltage)
6: Pulse input (100.0% corresponds
to 50.0 kHz)
7: AI1
8: AI2
9: Reserved
10: Length
11: Count value
12: Communication setting
13: Motor speed
14: Output current (100.0%
corresponds to 1000.0 A)
15: Output voltage (100.0%
corresponds to 1000.0 V)
16: Output torque (directional,
100.0% corresponds to 2 times of
rated motor torque)
19: Taper output
0
☆
F5-07 AO function selection
0
☆
F5-09 Maximum FMP output
frequency
0.01 to 100.00 kHz
50.00 kHz
☆
F5-10
AO1 zero offset
coefficient
-100.0% to +100.0%
0.0%
☆
F5-11
AO gain
-10.00 to +10.00
1.00
☆
F5-17
FMR output delay
0.0s to 3600.0s
0.0s
☆
Содержание MD810 Series
Страница 1: ...User Guide MD810 Series Standard Drive Multidrive System A04 Data code 19010518 User Guide...
Страница 37: ...2 Installation 36 External 24 V power supply Connect with the drive unit terminal Figure e Figure f Figure g...
Страница 38: ...2 Installation 37 Figure h Figure i Figure 2 7 HST 6004 HST 7004 DC soft charge unit installation...