5 Quick Commissioning
- 70 -
Operation
Para.
No.
Parameter Name
Default
Commission
Trial RUN
Start the drive unit through operating panel control, terminal I/O
control, or communication setting.
Perform the following trial run steps on the LED operating panel:
1)
Set F0-02 (Command source selection) to 0 (External LCD panel/
Commissioning software).
2)
Go to F8-56 (Jog by LED panel) to set the jog frequency. "JOG"
will be displayed.
3)
Hold down or
to forward or reverse.
Check if the running performance satisfies your application. If yes,
then go forward to the next step; if no, then go back to check.
If it is SVC or FVC
control
Adjust speed loop
parameters
F2-00 Speed loop proportional gain 1
Asynchronous
motor: 30
Synchronous
motor: 20
To achieve better
performance
0 to 100
F2-01 Speed loop integral time 1
0.500s
0.001s to 10.000s
F2-02 Switchover frequency 1
5.00 Hz
0.00 Hz to F2-05 (Switchover frequency 2)
F2-03
Speed loop proportional gain 2
20
1 to 200
F2-04 Speed loop integral time 2
1.000s
0.001s to 10.000s
F2-05 Switchover frequency 2
10.00 Hz
F2-02 (Switchover frequency 1) to F0-10 (Maximum frequency)
Finish