p52
Ver. 3.003 (24/4/03)
CONCEPT IQ. PLUS Programmer’s Manual.
ADDRESS
DEFAULT
FUNCTION
(Data Type)
i.e. The control function only occurs on the Invalid-to-Valid transition or “edge”.
This means the Area can still be controlled by other entities, if required, such as:
-User control via PIN codes and Keyswitches, etc.
-Automatic control via the Re-Autoarm function.
-Remote Control.
NOTES:
1) If a System Reset occurs and the TimeZone is currently Valid, the Area will Auto-arm.
2) Auto-arm will Force-arm the Area and will only auto-isolate Delayed Zone Types. Any other Zone Types that are un-sealed when the
Area arms, will go into alarm.
3) If Area Auto-Arming is programmed, an “Auto-Arm Pre-Warn Time” may be programmed in Address 907. Default = 255 Seconds.
4) If an Exit Delay applies to the Area, the Exit Delay will start at the end of the Auto-Arm Pre-Warn Time.
5) If Area Auto-Disarm function is required, program the Area Auto-Disarm Options in Address 559.
AREA 1 ARMING OPTIONS
AREA 2 ARMING OPTIONS
AREA 3 ARMING OPTIONS
AREA 4 ARMING OPTIONS
0 - No TimeZone Control
1 - Area Auto-Arms when TimeZone 1 becomes Valid.
3 - Area Auto-Arms when TimeZone 3 becomes Valid.
2 - Area Auto-Arms when TimeZone 2 becomes Valid.
4 - Area Auto-Arms when TimeZone 4 becomes Valid.
AUTO DISARMING OPTIONS
If an option is selected, the Area will Auto-Disarm when the TimeZone (If assigned in the Area Auto-Arming Options) becomes Invalid.
Area Auto-Arming Options are programmed in Addresses 551 (Area 1) to 554 (Area 4).
1 - Auto-Disarm Area 1.
2 - Auto-Disarm Area 2.
3 - Auto-Disarm Area 3.
4 - Auto-Disarm Area 4.
551
552
553
554
555-558
559
0 - No TZ Control
0 - No TZ Control
0 - No TZ Control
0 - No TZ Control
Spare
(Option Data)
1 - No
2 - No
3 - No
4 - No