Ver. 3.003
p85
CONCEPT IQ. PLUS Programmer’s Manual.
PRINTER OUPUT, REVIEW FORMAT
General Review is a history of events available to the Upload/Download software or direct
to the Printer Comms Task in real time. Events such as alarms, restores, tampers, open,
close and system inputs are time stamped and entered into Review. General Review
contains a maximum of 128 entries, once Review is full, older events are lost as new ones
are entered.
Unique to the IQ Plus is “Access Review” events such as REX button, Door Forced, Door
Open Too Long (DOTL), valid and invalid card read and access entry are all viewable (requires
an add-on to the Upload/Download software). Access Review contains a maximum of 42
entries, once Review is full, older events are lost as new ones are entered.
General Options can be set, to allow Access Review to be written to General Review, this
option should be used with caution because of the limited size of the Review buffer. When
this option is set, the Access Review entries will also be directed to the Printer Comms
Task for printing in real time.
When a serial port has been set
to the Printer Comms Task (Address 515 or 517
option 2), the Review history is sent to that serial port. A
SERIAL
printer is required
using the baud rate set for the serial port (Address 516 or 518, option 3 )(default is
9600) , 8 bits, no parity. Handshaking is not used.
The Review history is output in the format; “Date Time--Event Text <CR>”
Listed below are the Event Text used:
“AC Fail”, “Low Battery”, “Cabinet Tamper”, “Siren Monitor Alarm “, “LAN Fuse Fail”,
“Battery Fuse Fail”, “Comms Fail”, “System Reset “, “Keypad Lockout alarm”,
“Zone Self Test Fail alarm”, “Keypad Medical Alarm “, “Keypad Panic Alarm “,
“Keypad Duress Alarm “, “Keypad Fire Alarm “, “Zone n in Area n alarm”,
“Area n Closed by User n”, “Area n Home Armed by User n”,
“Area n Opened by User n”, “User n Unlock Door n—OK”,
“User n Unlock Door n—Denied”, “Door n Forced alarm”,
“Door n Open Too Long alarm”, “Invalid Card Presented at Door n”,
“Door n Unlocked by REX Button\n”
Where ... n = Zone/Area/User/Door Number.
Example of Review, printer output.
27/03/03 13:24:00--Door 4 Unlocked by REX Button
27/03/03 13:26:00--User 1 Unlock Door 4--OK
27/03/03 13:28:00--Door 4 Open Too Long Alarmed
27/03/03 13:30:00--Door 4 Open Too Long Restored
27/03/03 13:32:00--Door 4 Forced Alarmed
27/03/03 13:34:00--Door 4 Forced Restored
27/03/03 13:36:00--Area 3 Closed by User 1
27/03/03 13:38:00--User 4 Unlock Door 3--Denied
27/03/03 13:40:00--Area 3 Opened by User 1