p22
Ver. 3.003 (24/4/03)
CONCEPT IQ. PLUS Programmer’s Manual.
12.
ENABLE THE STROBE. (IF A STROBE IS CONNECTED TO “OUT1”)
NEXT 801
The Strobe output (OUT1) on the Controller is controlled by Auxiliary 1.
To enable the Strobe output, assign Event Type 1 - Burglary Alarm (Strobe), to Auxiliary 1 at Address 801.
11.
PROGRAM THE DAYLIGHT SAVING START AND END DATES.
NEXT 590 to 595
1 - Sunday
2 - Monday
3 - Tuesday
4 - Wedesday
5 - Thursday
6 - Friday
7 - Saturday
10.
PROGRAM THE CURRENT TIME AND DATE. (Master User Operation)
NEXT 33
Set the Real-Time Clock.
The Time, Date and Day of Week are programmed in 3 separate fields in the following order: hh:mm (1st Field); DD:MM:YY (2nd Field); day (3rd Field)
i.e. Hour, Hour; Minute, Minute; Day, Day; Month, Month; Year, Year; Day Of Week: (Sunday=1, Monday=2, Tues=3, Wed=4, Thurs=5, Fri=6, Saturday=7)
Key in the data for the current Field, then press <ENTER> to save the data in the current Field and advance to the next Field.
e.g.
1) 07:24 AM, 5th June, 2003. Monday.
0, 7, 2, 4, <ENTER>; 0, 5, 0, 6, 0, 3, <ENTER>; 2, <ENTER>.
2) 05:15 PM, 20th September, 2004. Thursday.
1, 7, 1, 5, <ENTER>; 2, 0, 0, 9, 0, 4, <ENTER>; 5, <ENTER>.
t
t
t
t
Address
Parameter
Range
Default
Address
Parameter
Range
Default
590
Daylight Saving Start Month
0 - 12
0
593
Daylight Saving End Month
0 - 12
0
591
Daylight Saving Start Week
1 - 5
5
594
Daylight Saving End Week
1 - 5
5
592
Daylight Saving Day-of-week In Start Week
1 - 7
1
595
Daylight Saving Day-of-week In End Week
1 - 7
1