p28
Ver. 3.003 (24/4/03)
CONCEPT IQ. PLUS Programmer’s Manual.
No Reporting.
Go to Step 30
“User Programming”
t
t
24.
PROGRAM THE TEST REPORT OPTIONS.
Test Report Period
DEFAULT: 7
NEXT 509
Program the number of Days between Test Reports from 0 (No Test Report) to 255.
Program the Time of Day when the Test Report will be transmitted.
Test Report Hour
DEFAULT: 3
NEXT 510
Program the Hour value from 0 to 23.
Test Report Minute
DEFAULT: 30
NEXT 511
Program the Minute value from 0 to 59.
25.
PROGRAM THE DIALER LOCKOUT OPTION FOR ZONE INPUTS IF REQUIRED.
NEXT 651 to 666
23.
PROGRAM THE MAXIMUM DIAL ATTEMPTS.
NEXT 508
DEFAULT: 8 Attempts
Program the Maximum number of Dial Attempts from 1 to 16.
! CAUTION:
Communications Authority Regulations limit the maximum number of dial attempts.
In Australia the ACA specify a limit of 10 Attempts.
t
t
t
3
Dialer Lockout
Zone will only trigger the Dialer for the number of times specified in the “Dialer Swinger Shutdown Count”.
(Address 014)
Zone
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Address
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666