CONCEPT IQ. PLUS Programmer’s Manual.
Go to Step 17.
t
t
15A. PROGRAM AREA 1 ENTRY DELAY.
NEXT 531
DEFAULT: 30 Seconds
Program a value from 0 to 255 Seconds.
PROGRAM AREA 1 EXIT DELAY.
NEXT 541
DEFAULT: 60 Seconds
Program a value from 0 to 255 Seconds.
Multi-Area System
15B. PROGRAM AREA ENTRY DELAYS AS REQUIRED.
DEFAULT: 30 Seconds
Area 1 ................................................................... NEXT 531
Area 2 ................................................................... NEXT 532
Area 3 ................................................................... NEXT 533
Area 4 ................................................................... NEXT 534
Program a value from 0 to 255 Seconds.
PROGRAM AREA EXIT DELAYS AS REQUIRED.
DEFAULT: 60 Seconds
Area 1 ................................................................... NEXT 541
Area 2 ................................................................... NEXT 542
Area 3 ................................................................... NEXT 543
Area 4 ................................................................... NEXT 544
Program a value from 0 to 255 Seconds.
Single Area System
16.
PROGRAM THE TERMINAL ASSOCIATED AREA/S.
Terminal 1 ............................................................ NEXT 561
Terminal 2 ............................................................ NEXT 562
Terminal 3 ............................................................ NEXT 563
Terminal 4 ............................................................ NEXT 564
This determines the Area used for Arming/Disarming operations, Zone Lamp
display and Entry/Exit warnings. One of the following options can be selected:
0 - Multi-Area (All Areas are associated with the Terminal) DEFAULT.
1 - Area 1 is associated with the Terminal.
2 - Area 2 is associated with the Terminal.
3 - Area 3 is associated with the Terminal.
4 - Area 4 is associated with the Terminal.
t
t