p32
Ver. 3.003 (24/4/03)
CONCEPT IQ. PLUS Programmer’s Manual.
32.
DOOR FORCED
An Installer Code or Master User Code must be used to program this option
Programming the DOOR FORCED system input for DOOR 1, to operate an auxiliary.
This option can require the use of the plug-on auxiliary board
1) Key in your PIN, then Press
,
,
,
, then
,
,
then
This assigns event type 131 to Aux 10, when the door reed for DOOR1 goes into alarm without a valid request to
open the door, an output on auxiliary 10 will occur. Cleared with a valid PIN + OFF key.
31.
REX BUTTON ON TERMINAL
An Installer Code or Master User Code must be used to program this option
1) Key in your PIN, then Press
,
,
,
, then
to enable (
to disable ), default is disabled
This option enables the OFF key on the Terminal to act as a REX button
t
t
33.
DOOR OPEN TOO LONG (DOTL)
An Installer Code or Master User Code must be used to program this option
Programming the DOTL system input for DOOR 1, to operate an auxiliary.
This option can require the use of the plug-on auxiliary board
1) Key in your PIN, then Press
,
,
,
then
,
,
then
This assigns event type 141 to Aux 9, when the door reed for DOOR1 is open for longer than a period of time
equal to 4 times that of the lock open time set at address 909. Cleared with a valid PIN + OFF key or valid card badge.
t
No Access Options.
Go to Step 34
“Change Installer PIN”
t
t