Appendix
84
Installation and Maintenance
1.1.5 Pump Pressure Curves
Glycol has a higher viscosity than water. If admixtures of glycol are used, the pumping data of the circulation pump must be
corrected to match the mixing ratio.
1.1.5.1 Heat Pump Remaining Pump Head (after appliance losses)
70 % pump speed
100 % pump speed
0
1
2
3
4
5
6
7
8
9
0
5
10
15
20
25
30
35
40
Sy
stem
p
ressu
re
loss
(m
)
Flow rate (L/min)
Heat Pump Model
Units
4 kW
5 Kw
8 kW
10 kW
Design flow rate
l/m
11.47
14.33
22.93
28.67
Remaining Pump head (after appliance losses)
m
8.1
7.9
6.8
5.4
1.1.5.2 Ideal Heat Pump Magnetic Filter and Strainer Losses (Logic Air Pre-Plumbed Cylinders)
Heat Pump Model
Units
4 kW
5 kW
8 kW
10 kW
Design flow rate
l/m
11.47
14.33
22.93
28.67
Ideal Heat Pump Magnetic Filter and Strain losses
m
0.09
0.11
0.28
0.41
1.1.5.3 Central Heating Zone Pump Curves (Logic Air Pre-Plumbed Cylinders)
I
III
II
0
8.33
25
16.66
33.33
41.66
0
1
2
3
4
5
7
0
10
20
30
40
50
70
6
60
50
Wilo-Para
15/6, 25/6, 30/6
1~230 V - Rp½, Rp 1, Rp 1¼
p/kPa
H/m
l/min
Содержание Logic Air DHW IDEPLUHP180DUOPPSZ
Страница 80: ...80 Installation and Maintenance Appendix 1 1 SYSTEM SCHEMATICS 1 1 1 Schematics Key Legend...
Страница 81: ...Appendix 81 Installation and Maintenance 1 1 2 Logic Air Two Zone Pre Plumbed Cylinder with Integrated Buffer...
Страница 82: ...Appendix 82 Installation and Maintenance 1 1 3 Logic Air Single Zone Pre Plumbed Cylinder...
Страница 92: ...92 Installation and Maintenance Notes...
Страница 93: ...93 Installation and Maintenance Notes...