Section 9 - Fault Finding
78
Installation and Maintenance
FAUL
T FINDING
9.1.27 Back-up Boiler no Temperature Rise Fault
Check if Back-up boiler is at a fault condition.
9.1.28 Number of Heat Pump Starts Exceeded
Is there a blockage in the pipework between Indoor and
Heat Pumps?
Are Heating and Hot Water circuits correctly sized?
If a blockage exists in internal pipework then remove it.
Remove blockage
Correctly size heating and hot water
circuits
NO
NO
YES
YES
9.1.29 No Central Heating but Hot Water works OK
Are room thermostats calling for heat?
Are the radiator valves open?
Is diverter valve stuck in hot water position?
Replace indoor unit primary PCB
Set room thermostats to call for heat
Open radiator valves
Replace diverter valve
NO
NO
NO
YES
YES
NO