Section 9 - Fault Finding
72
Installation and Maintenance
FAUL
T FINDING
9.1.8 Room Thermostat 1 Fault
9.1.9 Room Thermostat 2 Fault
9.1.10 LPB (Cascade) Short-Circuit/Communication Fault
Replace batteries in Room Thermostat in central heating
zone 1. Does fault persist?
Replace batteries in Room Thermostat in central heating
zone 2. Does fault persist?
Is wiring from heat pump 1 indoor unit OCI345 to heat
pump 2 indoor unit OCI345 securely made at both ends ?
Move the Room Thermostat in central heating zone 1
nearer to the indoor unit. Does fault persist?
Move the Room Thermostat in central heating zone 2
nearer to the indoor unit. Does fault persist?
Replace heat pump 1 indoor unit OCI345. Does the
fault persist?
Replace Room Thermostat & smart interface
Replace Room Thermostats & smart interface
Replace heat pump 2 indoor unit OCI345
Connect wiring securely
NO
YES
YES
YES
YES
YES
YES