Section 5 - Commissioning
COMMISSIONING
59
Installation and Maintenance
CHANGING COMPENSATION CURVES
Having changed the Access Level from End User to Installer,
the following screen will be shown:-
Relay Test
Simulate Out’ Temp’
Heat Pump Status
Outside Temp’
Fault History
Versions
08:32
If you would like to change the compensation curves, rotate
the dial until the spanner symbol is highlighted and press the
dial then the following screen is shown:-
Complete parameter list
Quick Set Up
08:32
Rotate the dial until Complete Parameter List is highlighted
and press the dial then the following screen is shown:-
Back
1/1
08:32
09.05.2023
1 Time
1 Date
Time of day and date
08:32
Press the dial and rotate until Heating circuit 1 is shown.
Back
1/4
Schedule
21.0ºC
18.0ºC
700 Operating mode
710 Comfort temp setpoint
712 Reduced temp’ setpoint
Heating Circuit 1
08:32
Press the dial and then rotate so that Optimisation is
highlighted.
Back
3/4
180min
0min
Off
790 Optimum start control max
791 Optimum stop control max
850 Floor curing function
Heating Circuit 1
08:32
Press the dial and then rotate so that Optimisation is set to the
required setting.
Back
3/4
180min
0min
Off
790 Optimum start control max
791 Optimum stop control max
850 Floor curing function
Heating Circuit 1
08:32
Содержание Logic Air DHW IDEPLUHP180DUOPPSZ
Страница 80: ...80 Installation and Maintenance Appendix 1 1 SYSTEM SCHEMATICS 1 1 1 Schematics Key Legend...
Страница 81: ...Appendix 81 Installation and Maintenance 1 1 2 Logic Air Two Zone Pre Plumbed Cylinder with Integrated Buffer...
Страница 82: ...Appendix 82 Installation and Maintenance 1 1 3 Logic Air Single Zone Pre Plumbed Cylinder...
Страница 92: ...92 Installation and Maintenance Notes...
Страница 93: ...93 Installation and Maintenance Notes...