background image

NOTE:

Read the entire instruction manual before starting the installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may
cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance.
The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read
these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code
(NEC) for special installation requirements.
Recognize safety information. This is the safety-alert symbol

. When you see this symbol on the unit or in instructions and manuals, be alert

to the potential for personal injury.
Understand the signal word DANGER, WARNING, or CAUTION. These words are used with the safety-alert symbol. DANGER identifies the
most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death.
CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.

WARNING: Before installing or servicing system, always turn off main power to system. There may be more than 1

disconnect switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury or death.

INSTALLATION

PROCEDURE 1—CHECK EQUIPMENT AND JOBSITE

A.

Unpack Unit

Move to final location. Remove carton taking care not to damage unit.

B.

Inspect Equipment

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit service panel. (See
Fig. 2.) It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.

Fig. 1—Model HC1B

A92461

Installation and Start-Up Instructions

HC1B

Split-System
Heat Pump

Form:

IM-HC1B-02

Cancels:

IM-HC1B-01

Printed in U.S.A.

2-94

Catalog No.

92-33HC-1B2

Содержание HC1B

Страница 1: ...alert to the potential for personal injury Understand the signal word DANGER WARNING or CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal inju...

Страница 2: ...ction refer to TXV label in your unit If the indoor unit fan coil comes factory equipped with a bi flow hard shutoff TXV no TXV charge is required Install TXV kit to indoor coil as follows 1 Install suction tube adaptor 2 Install liquid flare to sweat adaptor 3 Connect external equalizer tube to fitting on suction tube adaptor 4 Position sensing bulb on horizontal portion of suction tube adaptor S...

Страница 3: ...to eliminate contamination and moisture in the system B Outdoor Units Connected to Factory Approved Indoor Units Outdoor unit contains correct system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field supplied or factory accessory tubing Check refrigerant charge for maximum efficiency See Procedure 9 Checking Charge C Refrigerant Tubing Connect tubi...

Страница 4: ...NEC A Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box See Fig 2 WARNING The cabinet must have an uninterrupted or unbroken ground according to NEC ANSI NFPA 70 1993 and local codes to minimize personal injury if an electrical fault should occur This may consist of electrical wir...

Страница 5: ... installing PROCEDURE 8 START UP 1 If equipped with a crankcase heater energize a minimum of 24 hrs before starting unit To energize heater only set thermostat at OFF position and close electrical disconnect to outdoor unit WARNING Service valve gage ports are equipped with Schrader valves To prevent personal injury wear safety glasses and gloves when handling refrigerant 2 Fully open liquid and v...

Страница 6: ... thermostat is closed The defrost mode is identical to the cooling mode except that the outdoor fan motor stops and second stage heat is turned on to continue warming the conditioned space PROCEDURE 9 CHECKING CHARGE Factory charge is shown on unit rating plate See Fig 2 CAUTION Compressor damage may occur if system is overcharged Adjust charge in cooling mode by following procedure shown on the s...

Страница 7: ...for secure physical connections of individual components within units Operation check of the heat pump system to determine actual working condition Necessary repair and or adjustment should be performed at this time Your servicing dealer may offer an economical service contract that covers seasonal inspections Ask for further details FOR THE RECORD Record the models and serial numbers of your new ...

Страница 8: ...FB5 FC4 FA4 FH4 FAN COILS USED WITH FB4 FB5 FC4 FA4 FH4 FAN COILS C W2 L G Y E O R THERMOSTAT SUBBASE INDOOR SPLICE CONNECTION OUTDOOR SPLICE CONNECTION DEFROST BOARD C W2 L G Y E O R ODT THERMOSTAT SUBBASE INDOOR SPLICE CONNECTION OUTDOOR SPLICE CONNECTION DEFROST BOARD SHR SHR EHR ODT ODT EMERGENCY HEAT RELAY FIELD SPLICE EHR ODT REMOVE WIRES FROM CRIMP NUT IN INDOOR FAN COIL WHEN INSTALLING OUT...

Отзывы: