2. Connection with Host System
105
[2] Virtual I/O Port
Virtual I/O ports are provided so that the controller can notify internal information. They are
used to warn a low power-supply voltage, notify errors, etc. Use these ports as necessary.
MSEL Virtual Input Ports (Internal Flags)
Port No.
Function
7000 Always
OFF
7001 Always
ON
7002
Reserved by the system
7003
Reserved by the system
7004
Reserved by the system
7005
Reserved by the system
7006
Critical system error = A message level error is present.
7007
Critical system error = An operation-cancellation level error is present.
7008
Critical system error = A cold-start level error is present.
7009
Reserved by the system
7010
A cause of drive-source cutoff is present (including a condition waiting for a cutoff cancellation input).
7011
A latch signal indicating that a cause of all-operation cancellation is present.
(This latch signal is used to recognize a cause of 1-shot reset. Latch cancellation: 7300-ON)
7012
A cause of all-operation pause is present (including a condition waiting for the restart switch to be pressed).
(Effective only in the auto operation recognition mode)
7013
A cause of all-servo-axis interlock is present (cause of all-operation pause + cause of interlock input port)
7014 to 7050 Reserved by the system
7051 to 7070 For future expansion
7071
In the AUTO mode
7072
During auto operation
7073 to 7100 Reserved by the system
7101
Program No. 01 is being executed (or paused).
~ ~
7228
Program No. 128 is being executed (or paused).
7229 to 7299 For future expansion
MSEL Virtual Output Ports (Internal Flags)
Port No.
Function
7300
A latch cancellation signal is output to cancel the latch signal indicating a cause of all-operation cancellation
(7011). (Unlatched only when the cause of operation cancellation is no longer present.)
(7300 is turned OFF after latch cancellation is attempted.)
7301 to 7380 For future expansion
7381 to 7399 Reserved by the system
7400 For
future
expansion
7401
Program No. 129 is being executed (or paused).
~
7527
Program No. 255 is being executed (or paused).
7528 to 7599 For future expansion
Содержание PSEL
Страница 2: ......
Страница 10: ......
Страница 18: ...8 Part 1 Installation ...
Страница 37: ...27 Part 1 Installation 2 2 axis specification with battery ...
Страница 382: ...372 Appendix Micro cylinder RCL Series Current limiting value ratio Push force N ...
Страница 476: ...466 Appendix ...
Страница 480: ...470 ...
Страница 485: ...475 ...
Страница 487: ...INTELLIGENT ACTUATOR SEL Language Programming Manual Eighth Edition ...
Страница 488: ......
Страница 490: ......
Страница 494: ......
Страница 518: ...24 ...
Страница 526: ...32 ...
Страница 831: ... 11 Actuator Control Declaration 337 Example DFIF 1 170 ...
Страница 1060: ......
Страница 1061: ......