3-20
Chapter 3
Installing the UPS
Examples of PowerTrust Connections in a System
Example 1: Single Expansion Cabinet System
(Field-Integrated)
Figure 3-11 shows a field-integrated system with one expansion cabinet. Note these
features:
• A second (switchless) PDU (identified as the UPS PDU) has been installed. This PDU
receives its power from the IEC320 C19 connector on the PowerTrust UPS.
• For this example, all peripherals in the cabinet are being powered via the UPS PDU. If
either the UPS or PDU ratings are insufficient to power all of the peripherals, the
switched PDU is still available for powering the additional peripherals, but they will
not be protected by the UPS.
• The system console is being powered from the UPS PDU.
• The system SPU is being powered from the 30A output of the PowerTrust UPS.
• The expansion cabinet fan is powered from the UPS PDU to ensure that the cabinet is
cooled in the event of power failure.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...