Appendix A
A-15
HP-UX UPS Monitor Error Messages
reboot(2) Messages
MESSAGE
ups_mond: UPS <tty special file name> no output - either
switch setting wrong on UPS or bad UPS
SEVERITY
Critical. No power output from the PowerTrust device configured as <tty
special file name>.
MEANING
No output voltage from PowerTrust unit. If the specified PowerTrust unit is a
critical PowerTrust unit, then the system will reboot.
CAUSE
The cause may be one of the following:
1. The Output On/Output Off switch setting on the PowerTrust unit is
incorrect.
2. The PowerTrust unit has been turned off programmatically.
3. The PowerTrust unit is faulty.
ACTION
Toggle the Output On/Output Off switch on the suspect PowerTrust unit. If
the output voltage is not restored by toggling the switch, replace the
PowerTrust unit.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...