A-40
Appendix A
HP-UX UPS Monitor Error Messages
Log-Only Messages
MESSAGE
ups_mond: UPS <tty special file name> could not execute
command <command string>; returned <string> - possible bad
signal cable
SEVERITY
Warning/Error. A command sent to the PowerTrust unit had unpredictable
results.
MEANING
After a command was sent to the PowerTrust device configured as <tty special
file name>, the status returned was not as expected for either success or
failure conditions.
CAUSE
Either the RS-232 communication link between the host and the PowerTrust
unit is intermittent, or the PowerTrust unit is faulty.
ACTION
1. Check the I/O hardware components that comprise the
communications link from the SPU to the PowerTrust unit.
2. Check the PowerTrust hardware for correct cable connections,
power-on/off condition, and front panel conditions.
3. If neither of the first two action steps above corrects the problem, the
PowerTrust unit is probably faulty and should be replaced.
MESSAGE
ups_mond: warning - shutdown delay or shutdown timer
parameter in configfile <configfilename> missing or not
greater than zero; using default
SEVERITY
Warning/Error.
MEANING
A value in the PowerTrust configuration file for setting the amount of delay
time before graceful shutdown is missing or has not been set. The default
value will be used instead.
CAUSE
The shutdown delay value in the PowerTrust configuration file is missing or
has not been set.
ACTION
Edit the PowerTrust configuration file to set the shutdown delay value.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...