Appendix D
D-17
Field Replaceable Units
Removal and Replacement Procedures
NOTE
After installing the Hardwire Conversion Kit, power-on the load, check that
the computer is not performing critical processes, then repeat the load test.
For procedures, refer to “Load Testing” in Chapter 5.
Also, after installing replacement UPS equipment, test it by power failing the
UPS. For procedures, refer to “Power Failing the UPS” in Appendix C.
Removing and Replacing North American Conversion Kit
WARNING
The following procedure should be performed by a qualified
electrician only.
The North American Conversion Kit contains the following items:
1- Metal plate preassembled with a 3-pin L6-30 twist-lock receptacle and a line cord
4- Torx screws (#25 10-32 x 1/2')
2- Labels
Tools required:
• #25 Torx driver
• Flat blade screwdriver
Removing the existing conversion plate (if any):
1. If the UPS is operating, shut it down using the following procedure:
a. Turn the Output On/Output Off switch to
Output Off
.
b. Turn the UPS/BATTERY switch to
DISABLE
.
c. Turn OFF the MAIN INPUT circuit breaker.
d. DISCONNECT THE LINE CORD FROM THE AC SOURCE.
2. Remove the four Torx screws holding the left Access Panel (see
4
in Figure 1-3) on the
rear panel and remove the panel.
3. Disconnect the input and output wires by loosening the screws on the terminal block.
See Figure D-2.
4. Remove the four Torx screws holding the conversion plate on the right and remove it.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...