Appendix A
A-7
HP-UX UPS Monitor Error Messages
Timer Controlled Power On/Off Messages
MESSAGE
ups_mond: Timer Controlled On value exceeds UPS <tty special
file name> maximum. The maximum value of <value> will be used
for this UPS.
SEVERITY
Warning. Turn-on date and time will be earlier than requested.
MEANING
The PowerTrust hardware does not support the requested length of time for
delay.
CAUSE
The entered Timer Controller On value was outside the range of the
PowerTrust unit's capability.
ACTION
Ensure that the requested turn-on date and time are within the range of the
PowerTrust unit's capability.
MESSAGE
ups_mond: Power Off request active; performing graceful
shutdown.
SEVERITY
Warning.
MEANING
The PowerTrust unit has begun a graceful shutdown of the system.
CAUSE
An entered Timer Controller date and time setting for powering off the
PowerTrust unit has been reached, and the PowerTrust unit has begun to
gracefully shutdown the system.
ACTION
None.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...