MPE/iX UPS Monitor Error Messages
Alarm Status Messages
MESSAGE
UPS LDEV <nnn> reports UPS "Overload" condition. (UPSERR
0198)
CAUSE
The specified PowerTrust unit reported an "Overload" condition. The
equipment being powered by the PowerTrust unit is drawing too much power
from the PowerTrust unit AC output. If the excessive power draw continues,
the PowerTrust unit may reach an "Overload Shutdown" condition.
ACTION
1. Reduce the load on the PowerTrust unit by powering off some
non-critical system component.
2. Check for an improper system hardware installation. Correct the
system installation to reduce the loading on the PowerTrust unit.
3. If the system installation is not the problem, find and replace the
faulty system hardware component that is overloading the
PowerTrust unit.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...