Appendix B
B-19
MPE/iX UPS Monitor Error Messages
Log-Only Status Messages
MESSAGE
UPS LDEV <nnn> initialization error: After trying several
times, the UPS Monitor has been unable to complete the
initialization sequence of I/O operations for this UPS
device. (UPSERR 0573)
CAUSE
Something is preventing the HP 3000 system from communicating with the
PowerTrust unit. The fault is possibly a bad I/O interface cable, or bad I/O
interface hardware at the system or at the PowerTrust unit. A PowerTrust
unit hardware malfunction may also be the cause.
ACTION
1. Check the I/O interface cable for correct attachment.
2. Check that the PowerTrust unit is powered on.
3. Check that the system I/O configuration is correct.
NOTE: Even after correcting cable or connection problems, the system must
be rebooted before the software will attempt to resume monitoring the UPS.
MESSAGE
UPS Monitor warning: Too many UPS devices have been
configured in the system I/O configuration files. The UPS
Monitor cannot monitor all of them; it will monitor as many
as it can. (UPSWRN 0577)
CAUSE
Incorrect system I/O configuration. The system I/O configuration, generated by
SYSGEN and NMMGR configurators, contains more than 128 PowerTrust
units, which is the maximum number that the UPS monitor can handle
simultaneously.
ACTION
Review and correct the system I/O configuration, reducing the number of
PowerTrust units specified in the configuration to an acceptable number.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...