HP-UX UPS Monitor Error Messages
Normal Operation Messages
MESSAGE
ups_mond: AC Power to all recognized, system critical UPSs
OK! System will not shutdown.
SEVERITY
Information. A previous critical or warning condition related to AC input
power has been corrected.
MEANING
Following an AC power failure affecting one or more critical PowerTrust units
on the system, normal AC power has been restored to all critical PowerTrust
units before either exhaustion of the battery reserve power, or a graceful
shutdown, occurred. The system has recovered from the power failure.
CAUSE
The system has recovered from an AC power failure that was short enough not
to exhaust the PowerTrust unit's battery reserve, or cause a graceful
shutdown.
ACTION
None.
Содержание PowerTrust A3589A
Страница 7: ...Contents Contents 5 ...
Страница 8: ...Contents 6 Contents ...
Страница 10: ...Contents 8 Figures ...
Страница 12: ...Contents 10 Tables ...
Страница 14: ...2 ...
Страница 20: ...Preface 8 ...
Страница 22: ...Preface 10 ...
Страница 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Страница 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Страница 62: ...1 40 Chapter1 Overview Support Information ...
Страница 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Страница 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Страница 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Страница 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Страница 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Страница 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...